A, use the product
Is suitable for rated voltage up to and including 0.6/1 kv power line for delivery of electricity.This product has strong resistance to electromagnetic interference, resistance to lightning and uniform electric field, and improve the characteristics of the power supply quality, especially for places with precision electronic devices, such as the computer center, the monitoring center of aeronautics and astronautics, intelligent building, etc.
Second, the standards
This product is designed and manufactured according to Q/HX - 15
Third, the model name
model | The product name | |
Copper core | Aluminum conductor | |
VV-P YJV-P | VLV-P YJLV-P | Polyvinyl chloride (cross-linked polyethylene) insulated metal shield PVC sheathed power cable |
VV22-P YJV22-P | VLV22-P YJLV22-P | Polyvinyl chloride (cross-linked polyethylene) insulated metal BingBiGang with armored PVC sheathed power cable |
VV32-P YJV32-P | VLV32-P YJLV32-P | Polyvinyl chloride (cross-linked polyethylene) insulated metal mask fine steel wire armored PVC sheathed power cable |
ZR-VV-P ZR-YJV-P | ZR-VLV-P ZR-YJLV-P | Flame retardant PVC (cross-linked polyethylene) insulated metal shielding sheathed power cable |
ZR-VV22-P ZR-YJV22-P | ZR-VLV22-P ZR-YJLV22-P | Flame retardant PVC (cross-linked polyethylene) insulated metal BingBiGang with armored PVC sheathed power cable |
ZR-VV32-P ZR-YJV32-P | ZR-VLV32-P ZR-YJLV32-P | Flame retardant PVC (cross-linked polyethylene) insulated metal mask fine steel wire armored PVC sheathed power cable |
NH-VV-P NH-YJV-P | - | Polyvinyl chloride (cross-linked polyethylene) insulated metal shield PVC sheathed fire-resistant power cable |
NH-VV22-P NH-YJV22-P | - | Polyvinyl chloride (cross-linked polyethylene) insulated metal BingBiGang with armored PVC sheathed fire-resistant power cable |
NH-VV32-P NH-YJV32-P | - | Polyvinyl chloride (cross-linked polyethylene) insulated metal mask fine steel wire armored PVC sheathed fire-resistant power cable |
Type: the metal shield of power cable is on the design structure and cross-linked polyethylene insulating power cable and PVC insulated power cable is different, on the model with a distinction between "-p" suffix, such as: v. v. - P, YJV - P, YJLV22 - P and so on.
Fourth, specifications
Type no. | Number of cores | Nominal cross section (mm2) | |
Copper core | Aluminum conductor | ||
VV-P、YJV-P ZR-VV-P、ZR-YJV-P NH-VV-P、NH-YJV-P | VLV-P、YJLV-P ZR-VLV-P、ZR-YJLV-P | 1 | 4-300 |
VV-P、YJV-P ZR-VV-P、ZR-YJV-P NH-VV-P、NH-YJV-P | VLV-P、YJLV-P ZR-VLV-P、ZR-YJLV-P | 2 | 4-185 |
VV22-P ZR-VV22-P、ZR-YJV22-P ZR-VV32-P、ZR-YJV32-P ZR-VV42-P、ZR-YJV42-P | VLV22-P ZR-VLV22-P、ZR-YJLV22-P ZR-VLV32-P、ZR-YJLV32-P ZR-VLV42-P、ZR-YJLV42-P | 2 | 4-185 |
VV-P、YJV-P ZR-VV-P、ZR-YJV-P NH-VV-P、NH-YJV-P | VLV-P、YJLV-P ZR-VLV-P、ZR-YJLV-P | 3 | 2.5 ~ 240 |
VV22-P ZR-VV22-P、ZR-YJV22-P ZR-VV32-P、ZR-YJV32-P ZR-VV42-P、ZR-YJV42-P | VLV22-P ZR-VLV22-P、ZR-YJLV22-P ZR-VLV32-P、ZR-YJLV32-P ZR-VLV42-P、ZR-YJLV42-P | 3 | 2.5 ~ 240 |
VV-P、YJV-P ZR-VV-P、ZR-YJV-P NH-VV-P、NH-YJV-P | VLV-P、YJLV-P ZR-VLV-P、ZR-YJLV-P | 3 + 1 | 4-240 |
VV22-P ZR-VV22-P、ZR-YJV22-P ZR-VV32-P、ZR-YJV32-P ZR-VV42-P、ZR-YJV42-P | VLV22-P ZR-VLV22-P、ZR-YJLV22-P ZR-VLV32-P、ZR-YJLV32-P ZR-VLV42-P、ZR-YJLV42-P | 3 + 1 | 4-240 |
VV-P、YJV-P ZR-VV-P、ZR-YJV-P NH-VV-P、NH-YJV-P | VLV-P、YJLV-P ZR-VLV-P、ZR-YJLV-P | 4 | 4-185 |
VV22-P、ZR-VV22-P ZR-YJV22-P、ZR-VV32-P ZR-YJV32-P、ZR-VV42-P ZR-YJV42-P、NH-VV22-P NH-YJV22-P、NH-VV32-P NH-YJV32-P、NH-VV42-P NH-YJV42-P | VLV22-P ZR-VLV22-P、ZR-YJLV22-P ZR-VLV32-P、ZR-YJLV32-P ZR-VLV42-P、ZR-YJLV42-P | 4 | 4-185 |
Five, the conditions of use
1, cable conductor long-term working temperature shall not exceed 70 ℃
2, short circuit, cable conductor of the highest temperature should not exceed 160 ℃
3, when laying the environment temperature is not lower than 0 ℃, lower than 0 ℃ should be in advance when heating cable laying, the minimum bending radius
4, single core cable should not less than 20 times of cable diameter
More than 5, cable is not less than 15 times of cable diameter
6, laying, on both ends of the shield should be reliable grounding, does not make the shield broken or loose, otherwise it will reduce the shielding effect