W102 integrated temperature transmitter

Security code: No
browse:
add time: 2016-11-08 15:16:21
recommendation:

Buy join the shopping cart

Thermal resistance categoryTemperature measurement rangePrecision gradeAllowable deviation
Cu- 50 ~ + 100±(0.30+0.006) |t|
Pt- 200 ~ + 500A grade±(0.15+0.002) |t|
Class B±(0.30+0.005) |t|
Note: the table t is the absolute value of the measured temperature, ℃.
2. The thermocouple
Degree,Tolerance level
Tolerance values℃ temperature rangeTolerance values℃ temperature range
KPlus or minus 1.5 ℃- 40 ~ + 375Plus or minus 2.5 ℃- 40 ~ + 333
±0.004|t|375 ~ 1000±0.0075|t|333 ~ 1200
EPlus or minus 1.5 ℃- 40 ~ + 375Plus or minus 2.5 ℃- 40 ~ + 333
±0.004|t|375 ~ 800±0.0075|t|333 ~ 900
S+ / - 1 ℃0 ~ + 1100Plus or minus 1.5 ℃0 ~ 600
±[1+0.003(t-1100)]1100 ~ 1600±0.0025|t|600 ~ 1600
B----
--±0.0025|t|600 ~ 1700
Note: the actual temperature t, allowing the temperature degrees are available, and can also be a percentage of the actual temperature, said taking large amounts.
2. Normal temperature insulation resistance
(1) thermal resistance.
Thermal resistance at ambient temperature for 15 ~ 35 ℃, relative humidity is not more than 80%, test voltage is 10 ~ 100 v (dc) electrode and outer casing of the insulation resistance between 100 m Ω or higher.
2. The thermocouple
Thermocouple in the environmental temperature is 20 + 15 ℃, relative humidity is not more than 80%, the test voltage for 500 + 50 v (dc) electrode and outer casing of the insulation resistance between 100 m Ω or higher.
3. The thermal response time
When the temperature appear step change, the instrument of current output signal changes to correspond to the step change of 50% of the time required, usually expressed as a tau 0.5, in general, tau 0.5 90 s or less.
4. The minimum insertion depth
Minimum in depth of not less than 50 mm.
5. Nominal pressure
Generally refers to the protection tube at room temperature by static external pressure and not broken, take 1.5 times the nominal pressure test pressure.Allows working pressure is not only related to protecting tube material, diameter, wall thickness, and structural forms, installation methods, inserting depth, and the temperature of the measured medium, flow velocity and variety.