1. The index number and measurement range
(1) heat resistance (t is the absolute value of the measured temperature, ℃.)
Thermal resistance category | Temperature measurement range | Precision grade | Allowable deviation |
Cu | - 50 ~ + 100 |
| ±(0.30+0.006) |t| |
Pt | - 200 ~ + 500 | A grade | ±(0.15+0.002) |t| |
Class B | ±(0.30+0.005) |t| |
2. Thermocouple (t for actual temperature, allowing the temperature degrees are available, and also can use the percentage of actual temperature, said taking large amounts.)
Degree, | Tolerance level |
Ⅰ | Ⅱ |
Tolerance values | ℃ temperature range | Tolerance values | ℃ temperature range |
K | Plus or minus 1.5 ℃ | - 40 ~ + 375 | Plus or minus 2.5 ℃ | - 40 ~ + 333 |
±0.004|t| | 375 ~ 1000 | ±0.0075|t| | 333 ~ 1200 |
E | Plus or minus 1.5 ℃ | - 40 ~ + 375 | Plus or minus 2.5 ℃ | - 40 ~ + 333 |
±0.004|t| | 375 ~ 800 | ±0.0075|t| | 333 ~ 900 |
S | + / - 1 ℃ | 0 ~ + 1100 | Plus or minus 1.5 ℃ | 0 ~ 600 |
±[1+0.003(t-1100)] | 1100 ~ 1600 | ±0.0025|t| | 600 ~ 1600 |
B | - | - | - | - |
- | - | ±0.0025|t| | 600 ~ 1700 |
2. Normal temperature insulation resistance
(1) thermal resistance
Thermal resistance at ambient temperature for 15 ~ 35 ℃, relative humidity is not more than 80%, test voltage is 10 ~ 100 v (dc) electrode and outer casing of the insulation resistance between 100 m Ω or higher.
2 thermocouple
Thermocouple in the environmental temperature is 20 + 15 ℃, relative humidity is not more than 80%, the test voltage for 500 + 50 v (dc) electrode and outer casing of the insulation resistance between 100 m Ω or higher.
3. The thermal response time
When the temperature appear step change, the instrument of current output signal changes to correspond to the step change of 50% of the time required, usually expressed as a tau 0.5, in general, tau 0.5 90 s or less.
4. The minimum in depth
Minimum in depth of not less than 50 mm.
5. Nominal pressure
Generally refers to the protection tube at room temperature by static external pressure and not broken, take 1.5 times the nominal pressure test pressure.Allows working pressure is not only related to protecting tube material, diameter, wall thickness, and structural forms, installation methods, inserting depth, and the temperature of the measured medium, flow velocity and variety.
Instrument types | instructions |
W100 | /□ | /□ | /□ | /□ | /□ | /□ | /□ | /□ | /□ | /□ |
Temperature sensing element type | Z |
|
|
|
|
|
|
|
|
| The thermal resistance |
R | thermocouple |
Temperature sensing element material | P1 | Pt100 |
P2 | Pt1000 |
C1 | Cu50 |
C2 | Cu100 |
K | K type thermocouple (nickel chrome - nickel silicon) |
E | E type thermocouple (nickel chrome - constantan) |
S | S type thermocouple (platinum rhodium 10 - platinum) |
B | B type thermocouple (30 - platinum rhodium platinum rhodium 6) |
R | R type thermocouple (platinum rhodium 13 - platinum) |
N | N type thermocouple (nickel chrome - nickel silicon silicon magnesium) |
J | J type thermocouple (iron - constantan) |
T | T copper-constantan thermocouples,) |
The instrument type | O | The assembling |
K | Armor type |
M | Wear resistant |
D | End face type |
L | Right Angle bend type |
W | Micro type |
H | Type of health |
Structure form | S | Single type |
T | The double only |
Precision grade | A | Meaning see technical characteristics in detail |
B |
The output form | U | (RTD) only the thermal resistance |
V | (mV) only the thermocouple |
The connection method | 01 | Without a fixed device type |
02 | Fixed screw type |
03 | Activity card set screw type |
04 | Fixed flange |
05 | Activity card flange type |
06 | Conical protection tube fixed screw type |
07 | Rectangular flange |
The cold end form | 1 | Simple type (compensation conductor) |
2 | The bop wiring box |
3 | Waterproof connector box |
4 | Explosion-proof wiring box |
5 | The connector type |
Protecting tube diameter | Metal protection tube | M0 | Phi is 16 |
M1 | Phi 20 |
M2 | Phi 10 |
M3 | Phi 8 |
M4 | Phi 12 |
Non-metallic protection tube | N0 | Phi is 16 |
N1 | Phi 25 (double) |
N2 | Phi 20 |
N3 | Phi (double layer or three layer 33) |
other | O5 | Other diameter (user-specified) |
Insert depth | -XXX | Length (user-specified) |
Selection, for example: W1010 - m0 ZP1OSBU - 023-023
W10 type temperature sensor assembly, Pt100 temperature sensing element for thermal resistance, B level precision, fixed screw thread connection, 16 stainless steel protecting tube diameter, waterproof connector, the inserting depth of 150 mm.