High voltage, low voltage overhead insulated power cable

Security code: No
browse:
add time: 2016-11-04 09:17:28
recommendation:

Buy join the shopping cart

1, use: suitable for AC rated voltage 35KV and below the overhead power line, using the requirements of high security, urban high-rise buildings and areas of the occasion.

2, the use of characteristics:

Rated voltage is 1, 10KV.

Long working temperature of cable:

Polyvinyl chloride (PVC), polyethylene (PE) insulation should not exceed 70;

Cross linked polyethylene (XLPE) insulation shall be no more than 90.

The maximum temperature of the cable conductor in short circuit (the longest duration is no more than 5 seconds);

PVC insulation is not more than 160;

PE insulation is not more than 150;

Cross linked polyethylene insulation is not more than 250.

The cable laying temperature should not be lower than -20 DEG C.

Allowable bending radius of the cable:

The 1KV cable

External diameter of cable D<25mm...... 4D;

Cable diameter D = 25mm...... 6D.

The 10KV cable

Single core cable 20 (D+d) + 0.5%.

Multi core cable 15 (D+d) 0.5%.

The actual outer diameter (mm) of the D----- cable;

Actual outside diameter (mm) of d------- conductor.