Flame retardant and fire resistant power cable
Scope of application
This product is suitable for AC rated voltage 0.6/1kv and below the power lines, power supply and distribution can be used
Use characteristics
1 rated voltage 0.6/1KV is Uo/U.
2 long term allowable working temperature of cable conductor:
The long-term working temperature of PVC insulated and oxygen insulated cable is not more than 70;
The long-term working temperature of XLPE insulation and oxygen separation layer cable is not more than 90.
3 the laying temperature of the cable should not be less than 0. Laying below 0 degrees C must be heated in advance.
4 bending radius:
Single core cable allows bending radius: 20 (D+d) + 5%
Multi core cable allows bending radius: 15 (D+d) + 5%
Actual outside diameter (mm) of D- cable samples
The actual diameter (mm) of the d- conductor
Type and name
Specification and scope
Product structure diagram
Examples of representation methods
Refractory copper conductor, PE insulated and PVC sheath, oxygen insulation layer power cable, fixed laying, rated voltage 0.6/1KV, 4 core, 70mm expressed as GNH-YJV 4 * 70.